I think that's the problem right there. I was assuming that the -ve is always tied to chassis ground but apparently not....
Announcement
Collapse
No announcement yet.
User Profile
Collapse
-
Where's my 24V ???
Troubleshooting a simple circuit today in a PD panel . There is a small 24V power supply on the DIN rail. .It has line voltage on the input and 24V DC on it's outputs across the (-ve) and (+ve) terminals. Schematic says the (+ve) is connected to a fuse and then runs onto the rest of the circuit.
I thought there was a break between (+ve) and the power supply side of the fuse because when i measured between the panel door grounding point and the power supply side of the fuse I wasn't getting 24V DC on the meter. Would I be right in saying the above condition would be true if the power supply...